Did 2 System heat maintenance, both units operating properly at this time. The downstairs unit is very old R22, I recommend replacing.
DCM2: Heat complete, replaced 16x20x1 and 20x20x1 filters. Both systems are heating at this time. Upstairs system indoor coils and drain line are dirty. Scheduled comfort advisor to come out and go over options with homeowner. Tuesday 1-2pm. Maintenance checklist attached.
DCM1 complete; Heat; (1) F16254 checked. System is fully functional. All components are operating within manufacturer specifications. Gas pressure and heat rise are within design parameters. Heat checklist attached. Repaired floor vents upstairs
Did Heat maintenance on 2 systems, both operating properly
Quoted in hvacbizpro and emailed over
Quoted new heat pump system
SS2 switch was tripped. Cleared drain line. System is functioning as designed. Drain line has very limited fall. If problem persist recommend installing a condensate pump.
No air conditioning upon arrival - homeowner stated that it was 85* inside and wouldn’t drop temperature Found start run relay(capacitor shorted out in outdoor unit Part under warranty from manufacturer till 2028 - Labor is not covered Replaced part and checked operation Fan FLA- .64 - .62 Comp. RLA-12.8 - 5.62, 7.77, 5.27 Pressures - 151(53)/346(106), 14*SH, 10*SC, 91*AMB, 64*SA, 78* RA Everything operating as should - its 80* inside and will take hours to cool ********* Set up Club Member again *********
DCM1 complete; AC; (1) F16251 replaced. System is fully functional. All components are operating within manufacturer specifications. Refrigerant pressures and temperatures are appropriate for indoor and outdoor conditions. AC checklist attached
Installed and setup WiFi extender