Completed start up, corrected indoor blower fault. Added 8lbs of R410. Diagnostic photo attached Indoor temperature sensor on System #2 is still faulty.
Removed old air handler and installed 3rd new trane air handler.
Removed and installed 2nd air handler
Removed and Installed one air handler and have one air handler ready to be removed. Unit 1 has issues starting up
DCM1 complete; AC; (2) Aprilaire changed. System is fully functional. All components are operating within manufacturer specifications. Refrigerant pressures and temperatures are appropriate for indoor and outdoor conditions. AC checklist attached.
Unit 1 and2 has already been diagnosed. Unit #4 the evaporator coil is leaking, low Freon. TWE6044AAA04A000- 20232696BA
Arrived to No Cool on 2nd floor System #1 : Model #TWE06044AAA03A00 Serial #20102751BA System #2 :Model #TWE06044AAA03A00 Serial #20101344BA Identified faulty remote temperature sensor on System #2. Reading 0 ohms of resistance through sensor. Replaced remote temperature sensor with System #1s remote temperature sensor to confirm fault, System #2 detected temperature and functioned as designed. Once system #2 was operating, identified low pressure lockout, identified belt had come off the indoor blower sheaves. Belt is in horrible condition, photo attached. Recommend replacing A42 belt. Put belt back on to test system, checked system, identified extremely low refrigerant levels, (diagnostics photos attached), identified two leaks in system. first leak identified in evaporator coil, coil is severely rusted, second leak identified on lineset, leak is on backside of horizontal portion of 90 degree elbow (photo attached). Factory charge is 10.5 pounds of R-410 based on system pressure
Did spm on both units, office running properly, had to adjust pressure settings on apartment unit,possibly a leak, will keep an eye on it. Apartment unit gas leaking at cutoff and flexible line, tightened and checked, not leaking.
Removed old package unit and installed new 4 ton carrier gas package unit. Installed new thermostat. Reconnected high voltage, low voltage, drain line and gas line. Tested system operations in heating and cooling.
Met Aladdin