Increased 6” duct to 8” duct. Fixed bypass damper so air will flow properly. Put screw in supply vent in bedroom.
Need to increase 6” supply duct from damper on the left of the supply plenum to an 8” to the wall stack
Identified failed capacitor 70 + 5, replaced capacitor and tested system. Functions as designed. Compressor amp draw 16.2, RLA 25.0. Fan amp draw 1.3, RLA 1.6