DCM3 : A/C complete, replaced (1) 14x25x1 and (2) 16x25x1 filters. All systems are functional and cooling at this time. Upstairs and master bedroom systems are out of manufacture specifications due to indoor capacitors being out of range. Upstairs system 12.5+-10 3.1, master bedroom system 7.5+-10 4.9. If indoor capacitors fail systems will not cool or heat. System’s refrigerant pressures and temperatures are appropriate for outdoor and indoor weather conditions at this time. Temp split of 17*18*18*. Photos and maintenance checklist attached. Replaced capacitors all systems are fully functional and operating within manufacturer specifications at this time. Capacitors are now in range and amp draws are appropriate.
DCM2 complete; Heat; (2) F16251 replaced. Systems are fully functional. All components are operating within manufacturer specifications. Gas pressures and temperature rises are within design tolerances. Heat checklist attached.
DCM3 complete; AC; (2) F16251, (1) F14251 replaced. All systems are fully functional. All components are operating within manufacturer specifications with exception. Refrigerant pressures and temperatures are appropriate for indoor and outdoor conditions. AC checklist attached Main Floor and Upstairs outdoor capacitors are out of tolerance Upstairs system slightly low on refrigerant