Customers say: The reviews exhibit a positive sentiment overall, with a slight inclination towards the positive. The technicians are described as knowledgeable, respectful, and helpful, providing clear explanations and addressing concerns. Customers appreciate the professionalism, efficiency, and politeness of the Dobbs team. Positive reviews highlight the quality of work, timely responses, and fair pricing. Customers express satisfaction with the services provided, mentioning the technicians' expertise, thoroughness, and ability to explain technical information in a way that is easy to understand. The positive reviews also mention the company's reliability, punctuality, and willingness to go the extra mile to ensure customer satisfaction. However, there are a few negative reviews that mention high costs and a perception of being overcharged. Additionally, some customers express dissatisfaction with the length of time taken to complete the work or the quality of the workmanship. Overall, the reviews suggest that Dobbs provides reliable and efficient HVAC services, with a focus on customer satisfaction and technical expertise. While there are some areas for improvement, the positive reviews outweigh the negative ones, indicating that Dobbs is a reputable and trustworthy company in the HVAC industry.
Always great service!
Rob was great!
Excellent service..provide excellent feedback and recommendations to keep repair cost low
Have been a Dobbs customer since Keith started the business. We’ve never been disappointed with his service technicians and the quality work they do.
Jonathen was wonderful! Courteous and professional and got the job done fast!
DCM2: AC complete, replaced (12) 12x24x1 and (2) 20x20x1 filters checked belt. RTU is from 2003 running on R22 refrigerant. System is operating properly at this time and refrigerant pressures and temperatures are appropriate for indoor and outdoor weather conditions however due to age of equipment multiple part failure is possible at anytime. Training rom system is fully functional and operating within manufacturer specifications at this time, refrigerant pressures and temperatures are appropriate for indoor and outdoor weather conditions.
DCM2 complete; Heat; (12) F12242 and (2) F20201 replaced. Systems are fully functional. All components are operating within manufacturers specifications. Gas pressure and temperature rise are within design parameters. Refrigerant pressure and temperature are appropriate for indoor and outdoor conditions. Heat checklist attached.
Arrived to replace old single wall flu vent with Double Wall flue vent Photo attached
DCM2: AC complete, checked (3) 16x25x4 filters. Both systems are fully functional however not operating within manufacturer specifications due to indoor capacitor on basement system being out of tolerance and outdoor capacitor on main floor system being out of tolerance. Refrigerant pressures and temperatures are appropriate for indoor and outdoor weather conditions. Photos and maintenance checklist attached.
DCM2: A/C complete, replaced (2) 16x25x1 and (1) 16x25x4 filters. Both systems are fully functional and operating within manufacturer specifications at this time. Refrigerant pressures and temperatures are appropriate for indoor and outdoor weather conditions. Temp split 17* main floor and 16* upstairs. Noticed flue vent rusted out recommend replacing both flue vents due to hole in one and other starting to form rust. Recommend replacing with double wall instead of single wall to better insulate flue.
DCM2 Complete: Filters (12) 12x24x2, (2) 20x20x1 and Belt (1) BX83 has been changed. All systems are fully functional all components are operating within manufacturer specifications. Refrigerant temperatures and pressures are appropriate for indoor and outdoor conditions. Class room unit drain was tilted up causing system to drain into secondary drain pan. Vacuumed water from secondary drain pan and corrected the orientation. System is draining properly now.
Removed old equipment and installed new Rheem 5 ton evaporator coil and A/c unit. Installed new coil safety switch and new composite pad for outdoor unit. Reconnected high voltage, low voltage, drain line and supply plenum. Tested system operations, set charge.
No air conditioning in bullpen and classroom Classroom- Water in aux. drain pan - checked charge on unit and operating 123(42)/311(98) 22*SH and 4.7*SC unit low on 410a - added 2lbs of 410a 124(42)/324(101) 10.5*SH and 8*SC - Trane calls for 8* SC Drained water from aux. drain pan Need to leak search unit Bullpen- 2 burnt wires on blower contactor - cut back and connected back to contactor - control board giving a fault code of 12 (unit locked out due to fan overload switch failure) BOR Blower Overload Relay was faulty not allowing fan or air conditioner to operate - bypassed for the time to get cooling on Need to replace relay (Bi-yearly service is due next week)
Signed proposal in hvacbizpro
Main floor system is extremely low on R22 refrigerant. Saturation temp in indoor coil is 6*. Superheat is 64* Factory charge on unit is 10 lbs with an additional 3 lbs to account for line length and evaporator. Homeowner request quote to replace coils. Furnace is 7 years old and may be compatible with some cooling equipment.