Job Locations and Reviews

Dobbs A.
Dobbs A. Checked in
DCM2: AC complete, replaced (12) 12x24x1 and (2) 20x20x1 filters checked belt. RTU is from 2003 running on R22 refrigerant. System is operating properly at this time and refrigerant pressures and temperatures are appropriate for indoor and outdoor weather conditions however due to age of equipment multiple part failure is possible at anytime. Training rom system is fully functional and operating within manufacturer specifications at this time, refrigerant pressures and temperatures are appropriate for indoor and outdoor weather conditions.
Cumming, GA 30041
Rob S.
Rob S. Checked in
DCM2 complete; Heat; (12) F12242 and (2) F20201 replaced. Systems are fully functional. All components are operating within manufacturers specifications. Gas pressure and temperature rise are within design parameters. Refrigerant pressure and temperature are appropriate for indoor and outdoor conditions. Heat checklist attached.
Cumming, GA 30041
Rob S.
Rob S. Checked in
Arrived to replace old single wall flu vent with Double Wall flue vent Photo attached
Cumming, GA 30041
Review
Always great service!
Jason - Cumming, GA 30041
Dobbs A.
Dobbs A. Checked in
DCM2: AC complete, checked (3) 16x25x4 filters. Both systems are fully functional however not operating within manufacturer specifications due to indoor capacitor on basement system being out of tolerance and outdoor capacitor on main floor system being out of tolerance. Refrigerant pressures and temperatures are appropriate for indoor and outdoor weather conditions. Photos and maintenance checklist attached.
Cumming, GA 30041
Dobbs A.
Dobbs A. Checked in
DCM2: A/C complete, replaced (2) 16x25x1 and (1) 16x25x4 filters. Both systems are fully functional and operating within manufacturer specifications at this time. Refrigerant pressures and temperatures are appropriate for indoor and outdoor weather conditions. Temp split 17* main floor and 16* upstairs. Noticed flue vent rusted out recommend replacing both flue vents due to hole in one and other starting to form rust. Recommend replacing with double wall instead of single wall to better insulate flue.
Cumming, GA 30041
Rob S.
Rob S. Checked in
DCM2 Complete: Filters (12) 12x24x2, (2) 20x20x1 and Belt (1) BX83 has been changed. All systems are fully functional all components are operating within manufacturer specifications. Refrigerant temperatures and pressures are appropriate for indoor and outdoor conditions. Class room unit drain was tilted up causing system to drain into secondary drain pan. Vacuumed water from secondary drain pan and corrected the orientation. System is draining properly now.
Cumming, GA 30041
Dobbs A.
Dobbs A. Checked in
Removed old equipment and installed new Rheem 5 ton evaporator coil and A/c unit. Installed new coil safety switch and new composite pad for outdoor unit. Reconnected high voltage, low voltage, drain line and supply plenum. Tested system operations, set charge.
Cumming, GA 30041
Keith D.
Keith D. Checked in
No air conditioning in bullpen and classroom Classroom- Water in aux. drain pan - checked charge on unit and operating 123(42)/311(98) 22*SH and 4.7*SC unit low on 410a - added 2lbs of 410a 124(42)/324(101) 10.5*SH and 8*SC - Trane calls for 8* SC Drained water from aux. drain pan Need to leak search unit Bullpen- 2 burnt wires on blower contactor - cut back and connected back to contactor - control board giving a fault code of 12 (unit locked out due to fan overload switch failure) BOR Blower Overload Relay was faulty not allowing fan or air conditioner to operate - bypassed for the time to get cooling on Need to replace relay (Bi-yearly service is due next week)
Cumming, GA 30041
Keith D.
Keith D. Checked in
Signed proposal in hvacbizpro
Cumming, GA 30041
Rob S.
Rob S. Checked in
Main floor system is extremely low on R22 refrigerant. Saturation temp in indoor coil is 6*. Superheat is 64* Factory charge on unit is 10 lbs with an additional 3 lbs to account for line length and evaporator. Homeowner request quote to replace coils. Furnace is 7 years old and may be compatible with some cooling equipment.
Cumming, GA 30041
Review
Rob was great!
Jason - Cumming, GA 30041
Review
Excellent service..provide excellent feedback and recommendations to keep repair cost low
Eric - Cumming, GA 30040
Review
Have been a Dobbs customer since Keith started the business. We’ve never been disappointed with his service technicians and the quality work they do.
Jason - Cumming, GA 30041
Review
Jonathen was wonderful! Courteous and professional and got the job done fast!
Donna - Cumming, GA 30040

"Great Customer Service and Follow Up"

5 stars
“The service I received from Dobbs was A-1. From the initial call, scheduling and end of service follow through, I received great communication and service. I was informed about the work needed, costs and there were no surprises! I am a very satisfied customer.”

"Great Company, Great Service!"

5 stars
“I have had nothing but great experiences with Dobbs Heating and Air. They do great work, give great advice, and make sure all your questions and concerns are answered. I definitely recommend them!”

"Impressed by Dobbs’ professionalism"

5 stars
“I have been so impressed by Dobbs’ professionalism and service! Thank you for keeping us cool in the summer and warm in the winter!”
~ Jacqueline Hudson, Satisfied Customer

"John was great"

5 stars
"John was great. I use DOBBS for both my business and home and would not trust anyone else with my HVAC needs.”
~ Jeremy Commins, Satisfied Customer

"Friendly, Courteous, and Knowledgeable"

5 stars
"Always friendly, courteous, and knowledgeable. I appreciate their prompt arrival or phone call if there is a delay.”
~ Lisa, Satisfied Customer